XPSUAF13AP
Back
XPSUAF13AP safety module, Harmony XPSU, Cat 4, potential free 2 NC, NO NC, 2 PNP, 24V AC or DC, screw
รหัสสินค้า
XPSUAF13AP
จำนวนสินค้า
สินค้าหมด
ค่าจัดส่ง
ไม่มีค่าจัดส่ง
฿18,100.00 (ส่วนลด 50%)
ราคา ฿9,050.00
รายละเอียดสินค้า
Range of product | Harmony Safety Automation |
---|---|
Product or component type | Safety module |
safety module name | XPSUAF |
safety module application | Monitoring antivalent contacts For emergency stop, guard and light curtain monitoring |
function of module | Emergency stop button with 2 NC contacts Guard monitoring with 1 or 2 limit switches Monitoring 2 PNP sensors Magnetic switch monitoring Light curtain monitoring RFID switch Monitoring of electro-sensitive protection equipment (ESPE) Proximity sensor monitoring |
Safety level | Can reach PL e/category 4 conforming to ISO 13849-1 Can reach SILCL 3 conforming to IEC 62061 Can reach SIL 3 conforming to IEC 61508 |
Safety reliability data | MTTFd > 30 years conforming to ISO 13849-1 Dcavg >= 99 % conforming to ISO 13849-1 PFHd = 1.13E-09 conforming to ISO 13849-1 HFT = 1 conforming to IEC 62061 PFHd = 1.13E-09 conforming to IEC 62061 SFF > 99% conforming to IEC 62061 HFT = 1 conforming to IEC 61508-1 PFHd = 1.13E-09 conforming to IEC 61508-1 SFF > 99% conforming to IEC 61508-1 Type = B conforming to IEC 61508-1 |
electrical circuit type | NC pair PNP pair Antivalent pair OSSD pair |
Connections - terminals | Removable screw terminal block, 0.2...2.5 mm² solid or flexible Removable screw terminal block, 0.25...2.5 mm² flexible with ferrule single conductor Removable screw terminal block, 0.2...1.5 mm² solid or flexible twin conductor Removable screw terminal block, 2 x 0.25...1 mm² flexible with ferrule without cable end, with bezel Removable screw terminal block, 2 x 0.5...1.5 mm² flexible with ferrule with cable end, with bezel |
[Us] rated supply voltage | 24 V AC - 15...10 % 24 V DC - 20...20 % |
Synchronisation time between inputs | 0.5 s 2 s 4 s |
---|---|
Type of start | Automatic/manual/monitored |
Power consumption in W | 2.0 W 24 V DC |
Power consumption in VA | 5.0 VA 24 V AC 50/60 Hz |
Input protection type | Internal, electronic |
safety outputs | 3 NO |
safety inputs | 2 safety input 24 V DC 5 mA |
maximum wire resistance | 500 Ohm |
Input compatibility | Normally closed circuit conforming to ISO 14119 XC limit switch conforming to ISO 14119 Mechanical contact conforming to ISO 14119 Normally closed circuit conforming to ISO 13850 Antivalent pair conforming to ISO 14119 OSSD pair conforming to IEC 61496-1-2 3-wire proximity sensors PNP |
[Ie] rated operational current | 5 A AC-1 for normally open relay contact 3 A AC-15 for normally open relay contact 5 A DC-1 for normally open relay contact 3 A DC-13 for normally open relay contact |
control outputs | 3 on/off configurable pulsed output |
Input/output type | Semiconductor pulsed diagnostic output 24 V DC, 20 mA Z1, not safety-related |
[Ith] conventional free air thermal current | 8 A |
Associated fuse rating | 10 A gG for NO relay output circuit conforming to IEC 60947-1 |
Minimum output current | 10 mA for relay output |
Minimum output voltage | 15 V for relay output |
Maximum response time on input open | 20 ms |
[Ui] rated insulation voltage | 250 V (pollution degree 2) conforming to EN/IEC 60947-1 |
[Uimp] rated impulse withstand voltage | 4 kV overvoltage category II conforming to EN/IEC 60947-1 |
Local signalling | LED (green) for power ON LED (red) for error LED (yellow) for start LED (yellow) for safety status LED (yellow) for safety input S12 LED (yellow) for safety input S22 |
Mounting support | 35 mm symmetrical DIN rail |
Depth | 120 mm |
Height | 100 mm |
Width | 22.5 mm |
Net weight | 0.200 kg |
Standards | IEC 60947-5-1 IEC 61508-1 functional safety standard IEC 61508-2 functional safety standard IEC 61508-3 functional safety standard IEC 61508-4 functional safety standard IEC 61508-5 functional safety standard IEC 61508-6 functional safety standard IEC 61508-7 functional safety standard ISO 13849-1 functional safety standard IEC 62061 functional safety standard |
---|---|
Product certifications | TÜV cULus |
IP degree of protection | IP20 (terminals) conforming to EN/IEC 60529 IP40 (housing) conforming to EN/IEC 60529 IP54 (mounting area) conforming to EN/IEC 60529 |
Ambient air temperature for storage | -25…85 °C |
Relative humidity | 5…95 % non-condensing |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 6.700 cm |
Package 1 Width | 13.700 cm |
Package 1 Length | 15.500 cm |
Package 1 Weight | 276.000 g |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 16 |
Package 2 Height | 30.000 cm |
Package 2 Width | 30.000 cm |
Package 2 Length | 40.000 cm |
Package 2 Weight | 5.100 kg |
Unit Type of Package 3 | P06 |
Number of Units in Package 3 | 128 |
Package 3 Height | 75.000 cm |
Package 3 Width | 60.000 cm |
Package 3 Length | 80.000 cm |
Package 3 Weight | 50.772 kg |