MTZ216H16X3PMD
Back
MTZ216H16X3PMD Circuit breaker, MasterPact MTZ2 16H1 (66kA/415VAC), 3P, 1600A, drawout, manually operated, MicroLogic 6.0X control unit
SKU
รหัสสินค้า
MTZ216H16X3PMD
Stock
จำนวนสินค้า
SOLD
Shipping
ค่าจัดส่ง
FREE
฿256,000.00 (Discount 50%)
Price ฿128,000.00
รายละเอียดสินค้า
Range | MasterPact |
---|---|
Product name | MasterPact MTZ2 |
Device short name | MTZ2 16 H1 |
Product or component type | Circuit breaker |
Device application | Distribution |
Poles description | 3P |
Protected poles description | 3D |
[In] rated current | 1600 A at 50 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
utilisation category | Category B |
[Icu] rated ultimate short-circuit breaking capacity | 66 kA Icu at 220/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 66 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 66 kA Icu at 500/525 V AC 50/60 Hz conforming to EN/IEC 60947-2 66 kA Icu at 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
Performance level | H1 66 kA 415 V AC |
Trip unit name | MicroLogic 6.0 X |
Trip unit technology | Electronic |
Trip unit protection functions | LSIG |
Control type | Manually operated ON/OFF push-button |
Mounting mode | Drawout |
[Ui] rated insulation voltage | 1000 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
---|---|
[Uimp] rated impulse withstand voltage | 12 kV conforming to EN/IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity | 66 kA at 220/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 66 kA at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 66 kA at 500/525 V AC 50/60 Hz conforming to EN/IEC 60947-2 66 kA at 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
[Icw] rated short-time withstand current | 66 kA 0.5 s conforming to EN/IEC 60947-2 66 kA 1 s conforming to EN/IEC 60947-2 36 kA 3 s conforming to EN/IEC 60947-2 |
[Icm] rated short-circuit making capacity | 145 kA (Icm) at 220/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 145 kA (Icm) at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 145 kA (Icm) at 500/525 V AC 50/60 Hz conforming to EN/IEC 60947-2 145 kA (Icm) at 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
Maximum breaking time | 25 ms |
maximum closing response time | 70 ms |
Mechanical durability | 25000 cycles with periodic preventive maintenance conforming to EN/IEC 60947-2 |
Electrical durability | 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
Power dissipation per pole | 390 W |
mounting support | Base plate Rails |
Upside connection | Rear Vertical |
downside connection | Rear Vertical |
Connection pitch | 115 mm |
Protection type | Overload protection (long time) conforming to ANSI 49 Instantaneous short-circuit protection conforming to ANSI 50 Short time short-circuit protection conforming to ANSI 51 Earth fault conforming to ANSI 51N |
Trip unit rating | 1600 A at 50 °C |
[Ir] long-time protection pick-up adjustment range | 0.4...1 x In adjustable in step of 1 A |
Long-time protection delay adjustment type tr | Adjustable in step of 0.5 s |
[tr] long-time protection delay adjustment range | 12.5…600 s at 1.5 x Ir 0.5…24 s at 6 x Ir 0.34…16.6 s at 7.2 x Ir |
Thermal memory | Yes |
[Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir adjustable in step of 0.5 x Ir with embedded HMI |
Short-time protection delay adjustment type tsd | Adjustable |
[tsd] Short-time protection delay adjustment range | 0.1…0.4 s I²t=on 0…0.4 s I²t=off |
[Ii] instantaneous protection pick-up adjustment range | 2...15 x In adjustable in step of 0.5 x In with embedded HMI Ii enable on/off |
[li mode] instantaneous delay adjustment range | 20...50 ms in standard |
[Ig] ground-fault protection pick-up adjustment range | With In > 400 A 0.2...1 x In adjustable in step of 0.1 x In with In <= 400 A 0.3...1 x In adjustable in step of 0.1 x In Ig enable on/off |
Ground-fault time delay adjustment type | Adjustable |
[tg] ground-fault protection time delay adjustment range | 0.1…0.4 s I²t=on 0…0.4 s I²t=off |
earth-leakage protection | Without |
Zone selective interlocking ZSI | With |
Network and machine diagnosis type | System (HMI) health state overview: circuit breaker health state standard) Contacts state: circuit breaker health state standard) MicroLogic service life: circuit breaker health state standard) Tripping cause indication: circuit breaker tripping cause standard) Identification card: diagnostic data standard) Configured alarms synthesis: diagnostic data standard) Monitored function: diagnostic data standard) Operation: diagnostic data standard) MicroLogic test: test standard) Protection test: test standard) Selectivity test: test standard) Trip context information: crisis management standard) Operation: advanced diagnostic standard) Breaker service life: circuit breaker health state standard) |
Type of measurement | Power meter |
Energy management | Measurement ,active, reactive and apparent energy (standard) Measurement ,electrical network (standard) Measurement ,energy (standard) |
Metering type | Current I1, I2, I3, In, Ig: maximum standard) Average voltage Vavg standard) Active power P, P1, P2, P3 standard) Reactive power Q, Q1, Q2, Q3 standard) Apparent power S, S1, S2, S3 standard) Power factor standard) Frequency standard) Total current harmonic distortion THD (I): inst, avg, avg min, avg max fundamental voltage standard) Total current harmonic distortion THD (I): inst, avg, avg min, avg max RMS voltage standard) Voltage V21, V32, V13, V1, V2, V3: instantaneous standard) Voltage V21, V32, V13, V1, V2, V3: minimum standard) Voltage V21, V32, V13, V1, V2, V3: maximum standard) Total voltage harmonic distortion THD (V): inst, avg, avg min, avg max fundamental voltage standard) Total voltage harmonic distortion THD (V): inst, avg, avg min, avg max RMS voltage standard) Demand current I1, I2, I3, In, Iavg standard) Demand power P, Q, S standard) |
Measurement voltage | 145.6…828 V AC 50/60 Hz per phase |
Frequency measurement range | 45…250 Hz |
Measurement accuracy | Power factor: +/- 1 % Active energy Ep IN/OUT/tot: +/- 1 % - 10...10 GWh Reactive energy Ep IN/OUT/tot: +/- 2 % - 10...10 GVARh Apparent energy Es IN/OUT/tot: +/- 1 % - 10...10 GVAh Unbalance current: +/- 0.5 % Frequency: +/- 0.005 Hz Voltage V21, V32, V13, VLLavg: +/- 0.5 % 208...690 x 1.2 V Voltage V21, V32, V13, VLNavg: +/- 0.5 % 120...400 x 1.2 V Apparent power S, S1, S2, S3, Sdemand: +/- 1 % Active power P, P1, P2, P3, Pdemand: +/- 1 % Reactive power Q, Q1, Q2, Q3, Qdemand: +/- 2 % Current I1, I2, I3, Iavg, Idemand for MTZ1: +/- 0.5 % 40...1600 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ2: +/- 0.5 % 40...4000 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ3: +/- 0.5 % 80...6300 x 1.2 A |
Accuracy class | Class 5: total current harmonic distortion THD (I) Class 0.5: unbalance voltage Class 1: active and reactive energy by pulse counting (+/- W.h, +/- VAR.h) Class 2: total voltage harmonic distortion THD (V) |
Display type | LCD display - 128 x 96 pixels |
Local signalling | 3 LEDs (red) for trip causes 1 LED (red/orange) for overload 1 LED (green) for ready to operate 1 LED (red/orange) for service |
Communication port protocol | Bluetooth 4.0 LE peer to peer 30 kbit/s conforming to IEEE 802.15.1 NFC peer to peer 28800 bauds conforming to ISO 15963 USB peer to peer 115 kbauds |
data recording | Min/max of instantaneous values Alarm logs Maintenance logs Event logs Time stamping Data logs |
Commissioning interface | EcoStruxure Power Commission |
end user smartphone application | EcoStruxure Power Device |
Locking options description | Padlock in OFF position Keylock in OFF position |
Provision for padlocking | 3 padlocks |
Width (W) | 422 mm |
Height (H) | 352 mm |
Depth (D) | 300 mm |
Net weight | 90 kg |
standards | EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 61010-1 |
---|---|
product certifications | IECEE CB Scheme |
Pollution degree | 3 conforming to EN/IEC 60947-1 |
Overvoltage category | IV conforming to EN/IEC 61010-1 |
IP degree of protection | IP30 conforming to EN/IEC 60529 |
IK degree of protection | IK07 conforming to EN/IEC 62262 |
Environmental characteristic | Wet location not approved for use conforming to EN/IEC 61010-1 |
Electromagnetic compatibility | Electrostatic discharge immunity test conforming to EN/IEC 61000-4-2 Susceptibility to electromagnetic fields conforming to EN/IEC 61000-4-3 Electrical fast transient/burst immunity test conforming to EN/IEC 61000-4-4 1.2/50 µs shock waves immunity test conforming to EN/IEC 61000-4-5 Conducted RF disturbances A conforming to EN/IEC 61000-4-6 Conducted and radiated emissions conforming to CISPR 22 |
Measurement category | Category IV conforming to IEC 61010-2-30 |
Ambient air temperature for operation | -25…70 °C (operating) -35 °C (for start-up of product) |
Ambient air temperature for storage | -40…85 °C |
Relative humidity | 0…95 % conforming to IEC 60068-2-30 |
Operating altitude | <= 2000 m without derating <= 3000 m 99 % of In <= 4000 m 96 % of In <= 5000 m 94 % of In |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 70 cm |
Package 1 Width | 60 cm |
Package 1 Length | 80 cm |
Package 1 Weight | 90 kg |